DocumentCode
1048230
Title
The Vincent 220-Kv. Transmission Line Engineering and Construction Features
Author
Carlson, C.B. ; Michener, H.
Author_Institution
Southern California Edison Company, Los Angeles, Calif.
fYear
1926
Firstpage
1053
Lastpage
1063
Abstract
This paper deals with the design and construction of the third 220,000-volt line between Los Angeles and Big Creek, giving the results and brief descriptions of the research engineering investigations which were carried out in connection with the design. The salient features of the line are: Terminals??Big Creek No. 3 and Gould Switching Station, near Los Angeles. Length??223.5 mi. Route??Direct route with few angles. Dead-ends??Dead-ends only at station terminals and heavy angles. Small angles??Small angles up to 11 deg. 40 min., in some cases, turned on suspension insulators. Conductors??Steel reinforced aluminum. 1,033,500 cir. mils aluminum, 54 strands. 134,000 cir. rails steel, 7 strands. Weight: 1.33 lb. per ft. Diameter: 1.247 in. Overhead Ground Wire??None. Towers??Towers of high elastic limit steel. Height of standard towers, 64 ft. to crossarm. Height of anchor tower, 56 ft. to crossarm. Weight of standard tower, 8890 lb. Weight of anchor tower, 13,600 lb. Tower Footings-Grillage footings in earth. For standard towers, 4ft. 8 in. sq. at base and 8 ft. deep. Weight, 2040 lb. For anchor towers, 7ft. 6 in. sq. at base and 9 ft. deep. Weight, 6720 lb. Tower Extensions-Height 7, 14, or 21 ft. Any of these heights may be placed on any or all corners of the tower and in a few special cases in combination with an additional 14-ft. extension on all corners. Insulators??10-in. cap and pin having minimum combined electrical and mechanical strength of not less than 18,000 lb.
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1926.5061301
Filename
5061301
Link To Document