DocumentCode
1048543
Title
Staged Fault Testing of Leased Audio-Tone Relaying Channels Subject to Ground Potential Rise and Induced Voltage
Author
Berke, I.R. ; Geer, E.W., Jr. ; Tucker, D.R.
Author_Institution
Bell Telephone Laboratories
Issue
1
fYear
1973
Firstpage
89
Lastpage
97
Abstract
A series of staged power-fault tests was conducted by the U. S. Bureau of Reclamation with the Bell System participating. One of the main purposes of these tests was to observe the effects of power-system disturbances on leased audio-tone relaying channels. Interference on these circuits was minimized by using bifilar-wound loading coils to avoid signal modulation effects; high-potential testing of telephone cable facilities ensured adequate dielectric strength. In addition, a communication-facility electrical protection system was installed which employed longitudinal drainage that was applied as needed to mitigate 60-Hz potentials introduced into the telephone plant.
Keywords
Circuit faults; Circuit testing; Coils; Interference; Power system relaying; Protective relaying; Relays; System testing; Telephony; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1973.293597
Filename
4075041
Link To Document