Title :
Switching Impulse Characteristics of UHV Station Post Insulators
Author :
Hileman, A.R. ; Askins, H.W.
Author_Institution :
Westinghouse Electric Corporation
Abstract :
Switching impulse tests were performed on single-column station post insulators having heights from 5 to 20 feet mounted atop grounded support structures having heights from 8 to 20 feet. Wavefronts of 120- and 1000-¿s were used. Results can be used to obtain preliminary estimates of requirements for EHV and UHV stations.
Keywords :
Costs; Flashover; Ground support; Impulse testing; Insulation; Insulator testing; Laboratories; Performance evaluation; Steel; Voltage;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :