• DocumentCode
    1049341
  • Title

    Instability in Transformer Banks

  • Author

    Gould, King E.

  • Author_Institution
    Research Division, Dept. of Elect. Engg., Mass. Inst. of Tech., Cambridge, Mass.
  • fYear
    1927
  • Firstpage
    676
  • Lastpage
    682
  • Abstract
    This paper considers the instability which sometimes occurs in banks of transformers supplying a capacity load when certain harmonics in the primary current are suppressed, either by the type of transformer connections or by a resonant circuit in series with the primary of the transformer, and the similarity between the several unstable circuits is pointed out. Curves showing the triple-frequency voltage distortion as a function of the capacity load have been included for two of the unstable circuits. For one case, oscillograms taken during the instablity are shown. An explanation, substantiated by actual analyses, has been brought forward for the simplest unstable circuit, consisting of three branches connected in Y across a three-phase line with balanced, sinusoidal line voltages, with the neutral unconnected, each branch of the Y consisting of an iron-cored reactance in parallel with a capacity. This explanation is extended to the other cases, two with experimental evidence as justification, and the third by analogy only.
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1927.5061404
  • Filename
    5061404