• DocumentCode
    1049398
  • Title

    Measurement of Shunt Reactor Loss at High Voltage with an Alternating Current Comparator Bridge

  • Author

    Moore, William J M ; Raftis, F.A.

  • Author_Institution
    National Research Council of Canada
  • Issue
    2
  • fYear
    1973
  • fDate
    3/1/1973 12:00:00 AM
  • Firstpage
    662
  • Lastpage
    667
  • Abstract
    The application of a high voltage capacitance bridge based on the current comparator to the measurement of the loss angle of high voltage shunt reactors is described. Measurements on three core-less 55 MVA, 735 kV single phase shunt reactors are discussed and a comparison is made with the results of a calorimetric determination of loss which indicates agreement to better than 2 percent. Other bridge techniques for this type of measurement are reviewed.
  • Keywords
    Bridge circuits; Capacitance; Current measurement; Inductors; Loss measurement; Phase measurement; Power measurement; Reactive power; Shunt (electrical); Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1973.293770
  • Filename
    4075123