DocumentCode
1049398
Title
Measurement of Shunt Reactor Loss at High Voltage with an Alternating Current Comparator Bridge
Author
Moore, William J M ; Raftis, F.A.
Author_Institution
National Research Council of Canada
Issue
2
fYear
1973
fDate
3/1/1973 12:00:00 AM
Firstpage
662
Lastpage
667
Abstract
The application of a high voltage capacitance bridge based on the current comparator to the measurement of the loss angle of high voltage shunt reactors is described. Measurements on three core-less 55 MVA, 735 kV single phase shunt reactors are discussed and a comparison is made with the results of a calorimetric determination of loss which indicates agreement to better than 2 percent. Other bridge techniques for this type of measurement are reviewed.
Keywords
Bridge circuits; Capacitance; Current measurement; Inductors; Loss measurement; Phase measurement; Power measurement; Reactive power; Shunt (electrical); Voltage;