    RF-Based Partial Discharge Early Warning System for Air-Insulated Substations

  • Author

    Portugués, Iliana E. ; Moore, Philip J. ; Glover, Ian A. ; Johnstone, Carl ; McKosky, Ralph H. ; Goff, Mark B. ; Van Der Zel, Luke

  • Author_Institution
    Elimpus Ltd., Bellshill
  • Volume
    24
  • Issue
    1
  • fYear
    2009
  • Firstpage
    20
  • Lastpage
    29
  • Abstract
    Partial discharges (PDs) generate wideband radio-frequency interference which can be used for noninvasive monitoring of discharges. This paper presents a novel method based on this principle for PD monitoring of substations. The significant advantage of this method lies in the ability to detect PD sources in energized equipment anywhere within a substation compound during normal operating conditions. The results obtained from the prototypes installed in the U.K. and U.S. substations are reported. Results include correlation with apparent charge and daily recordings obtained before, during, and after the failure of a 132-kV current transformer and 69-kV voltage transformer.
  • Keywords
    monitoring; partial discharges; power transformers; substations; RF-based partial discharge early warning system; air-insulated substations; current transformer; noninvasive monitoring; voltage 132 kV; voltage 69 kV; voltage transformer; Alarm systems; Current transformers; Fault location; Partial discharges; Prototypes; Radio frequency; Radiofrequency interference; Substations; Voltage transformers; Wideband; Apparent charge; condition monitoring; impulsive noise; location; partial discharge; radiometric monitoring;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2008.2005464
  • Filename
    4729811