DocumentCode
1049969
Title
Research at Project UHV on the Performance of Contaminated Insulators Part I Basic Problems
Author
Kawai, Mikio
Author_Institution
General Electric Company
Issue
3
fYear
1973
fDate
5/1/1973 12:00:00 AM
Firstpage
1102
Lastpage
1110
Abstract
The basic contamination research problems at Project UHV are discussed. Results of flashover tests on 27 types of insulators are presented with discussions on the test method. The performance of insulators is found not to be proportional to the leakage distance, and the influence of the shape of the insulator unit on its performance is demonstrated.
Keywords
Contamination; Flashover; Insulation; Insulator testing; Power & Energy Society; Probability; Shape; System testing; Tellurium; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1973.293677
Filename
4075179