DocumentCode
1050609
Title
A Study on Dynamic Voltage Distribution on Contaminated Insulator Surface
Author
Baker, A.C. ; Kawai, M.
Author_Institution
The Detroit Edison Co.
Issue
5
fYear
1973
Firstpage
1517
Lastpage
1524
Abstract
Dynamic voltage distribution on an insulator unit was investigated before and during scintillation activity. A simple method for the measurements of voltage distribution was successfully developed. It was observed that some parts of the leakage distance do not function during scintillations, and therefore the concept of "effective leakage distance" was introduced. A good correlationship between " effective leakage distance" and flashover voltage was found.
Keywords
Flashover; Glazes; Insulation; Insulator testing; Pollution measurement; Shape; Surface contamination; Surface impedance; Transmission lines; Voltage measurement;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1973.293696
Filename
4075242
Link To Document