DocumentCode :
1050747
Title :
Inductive Test Circuit for a Fast Acting HVDC Interrupter
Author :
Hofmann, G.A. ; Long, W.F. ; Knauer, W.
Author_Institution :
Hughes Research Laboratories
Issue :
5
fYear :
1973
Firstpage :
1605
Lastpage :
1614
Abstract :
A unique test facility utilizing the inductive energy storage principle has been constructed in order to examine the characteristics of a fast acting HVDC interrupter. The facility is capable of producing currents up to 10, 000 A, developing voltages up to 200 kV, and storing energies up to 125 kJ. It is able to closely simulate the operational stresses encountered in the interruption of dc current. Experimental and computer results illustrate the operating characteristics of the facility.
Keywords :
Circuit breakers; Circuit faults; Circuit testing; HVDC transmission; Impedance; Interrupters; Stress; Switches; Switching circuits; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1973.293708
Filename :
4075254
Link To Document :
بازگشت