• DocumentCode
    1050768
  • Title

    Insulation Coordination for Gas Insulated Substations

  • Author

    Anderl, Helfried W. ; Wagner, Charles L. ; Dodds, Thomas H.

  • Author_Institution
    Westinghouse Electric Corporation
  • Issue
    5
  • fYear
    1973
  • Firstpage
    1622
  • Lastpage
    1630
  • Abstract
    This paper presents the development of BIL (Basic Lightning Impulse Insulation Level) ratings for SF6 gas insulated substations from 72.5 kV to 765 kV. The unique properties of the gas insulated substation are analyzed and insulation coordination design techniques are utilized to determine BIL ratings for the substation equipment, other than the transformer, with a lightning arrester located at the entrance terminals. The resulting analysis shows that, in general, the required BIL level of apparatus for gas insulated systems can be lower than for conventional equipment because of lower surge impedance and shorter lengths of the gas insulated bus.
  • Keywords
    Dielectrics and electrical insulation; Gas insulation; Impedance; Lightning; Oil insulation; Power transformer insulation; Substations; Sulfur hexafluoride; Surges; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1973.293710
  • Filename
    4075256