DocumentCode :
1050768
Title :
Insulation Coordination for Gas Insulated Substations
Author :
Anderl, Helfried W. ; Wagner, Charles L. ; Dodds, Thomas H.
Author_Institution :
Westinghouse Electric Corporation
Issue :
5
fYear :
1973
Firstpage :
1622
Lastpage :
1630
Abstract :
This paper presents the development of BIL (Basic Lightning Impulse Insulation Level) ratings for SF6 gas insulated substations from 72.5 kV to 765 kV. The unique properties of the gas insulated substation are analyzed and insulation coordination design techniques are utilized to determine BIL ratings for the substation equipment, other than the transformer, with a lightning arrester located at the entrance terminals. The resulting analysis shows that, in general, the required BIL level of apparatus for gas insulated systems can be lower than for conventional equipment because of lower surge impedance and shorter lengths of the gas insulated bus.
Keywords :
Dielectrics and electrical insulation; Gas insulation; Impedance; Lightning; Oil insulation; Power transformer insulation; Substations; Sulfur hexafluoride; Surges; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1973.293710
Filename :
4075256