• DocumentCode
    1051232
  • Title

    Transient Response of a Floor Net Used as Ground Return in High Voltage Test Areas

  • Author

    Dénommé, Florent ; Trinh, N. Giao ; Mukhedkar, Dinkar

  • Author_Institution
    Hydro-Québec Institute of Research
  • Issue
    6
  • fYear
    1973
  • Firstpage
    2007
  • Lastpage
    2014
  • Abstract
    As the test voltage level increases, it becomes more and more difficult to protect the control and measuring cables from the disturbances generated during the tests. To cope with this problem, new high voltage laboratories are nowadays equiped with a copper floor net used as ground return. This paper presents a theoretical analysis of the transient response of such a ground return system. The calculated performances compare favorably with experimental results obtained with the ground return system of the high voltage laboratory at IREQ, and can apply to the selection of the proper ground return system in new high voltage test areas.
  • Keywords
    Cables; Copper; Floors; Impedance; Laboratories; Performance evaluation; System testing; Transient analysis; Transient response; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1973.293581
  • Filename
    4075303