• DocumentCode
    1051441
  • Title

    The Use of Single-Phase Overhead Test Lines and Test Cages to Evaluate the Corona Effects of EHV and UHV Transmission Lines

  • Author

    Comber, M.G. ; Zaffanella, L.E.

  • Author_Institution
    GENERAL ELECTRIC COMPANY
  • Issue
    1
  • fYear
    1974
  • Firstpage
    81
  • Lastpage
    90
  • Abstract
    Economic considerations often limit the use of full-scale 3-phase test lines for the investigation of transmission-line corona effects. Testing of a large number of different conductor configurations can be more conveniently and efficiently carried out on comparatively short sections of conductors on single-phase test lines and in test cages. Techniques for measuring the single-phase corona performance of conductors are presented, along with a discussion of means by which the observed data can be used to determine the corona performance of 3-phase transmission lines.
  • Keywords
    Conductors; Corona; Councils; Geometry; Power overhead lines; Rain; Testing; Transmission line measurements; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1974.293918
  • Filename
    4075325