• DocumentCode
    1052307
  • Title

    A Laboratory Study on RI, TVI and an of Insulator Strings Under Contaminated Condition

  • Author

    Sawada, Yoshitsugu ; Fukushima, Mitsuo ; Yasui, Mitsuru ; Kimoto, Iwao ; Naito, Katsuhiko

  • Author_Institution
    Central Research Institute of Electric Power Industry
  • Issue
    2
  • fYear
    1974
  • fDate
    3/1/1974 12:00:00 AM
  • Firstpage
    712
  • Lastpage
    719
  • Abstract
    This paper reports the results of a laboratory study on radio interference ( RI), television interference (TVI) and audible noise (AN) of insulator strings for transmission lines of 154- , 275- and 500-kV classes. When insulators are contaminated and wetted, RI, TVI and AN becompe pronounced. The RIV, TVI and AN from insulator strings that were artificially contaminated with salt and kaolin were measured under artificial fog. Also, investigated were the ratio of TV signal intensity (S) to insulator noise intensity (N), and its degree of interference to TV picture.
  • Keywords
    Conductors; Hardware; Insulator testing; Laboratories; Partial discharges; Pollution measurement; Power transformer insulation; Power transmission lines; TV interference; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1974.294034
  • Filename
    4075408