• DocumentCode
    1052590
  • Title

    A Comparative Study of the Corona Performance of Conductor Bundles for 1200 KV Transmission Lines

  • Author

    Trinh, N. Giao ; Maruvada, P. Sarma ; Poirier, Benny

  • Author_Institution
    Hydro-Québec Institute of Research (IREQ)
  • Issue
    3
  • fYear
    1974
  • fDate
    5/1/1974 12:00:00 AM
  • Firstpage
    940
  • Lastpage
    949
  • Abstract
    As part of a general study on the possible use of UHV transmission lines in the range of 1200 kV for the James Bay Project, the corona performance of four conductor bundles -6 ×1. 823", 6 ×1. 998", 8 ×1. 63 " and 8 ×1.823"-has been studied in outdoor test cages under conditions of heavy artificial rain and fair weather. The radio interference, audible noise and corona losses of the four conductor bundles have been measured in the test cages, and the corresponding long line levels have been evaluated. The results show that of the four bundles tested the 8 ×1.63" conductor bundle gives the best corona performance. However, ice loading conditions may dictate the use of a six conductor bundle, in which case the 6 ×1.823" conductor bundle seems to give a marginally acceptable corona performance.
  • Keywords
    Acoustic noise; Conductors; Corona; Electromagnetic interference; Ice; Loss measurement; Noise measurement; Rain; Testing; Transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1974.294013
  • Filename
    4075439