DocumentCode :
1052605
Title :
69KV Ungrounded Neutral Tee Joints for Solid Dielectric Cable System
Author :
Balaska, T.A. ; Blais, L.D. ; Mc Beath, R.H.
Author_Institution :
Bishop Electric Co.
Issue :
3
fYear :
1974
fDate :
5/1/1974 12:00:00 AM
Firstpage :
950
Lastpage :
959
Abstract :
This reports the development, testing, installation, and operation of 69Kv ungrounded neutral tee joints for a crosslinked polyethylene (XLPE) cable circuit, which is the sole supply for a downtown urban renewal area in Lexington, Kentucky. The total circuit length is 3030 feet, consisting of three sections, the longest being 1630 feet. Conductor connections were made with a heat-fusion process. Joint dielectric consisted of self-amalgamating ethylene propylene tape. The circuit has been in operation since the late Spring of 1971.
Keywords :
Aluminum; Cable shielding; Circuit testing; Cities and towns; Conductors; Dielectrics; Polyethylene; Power cables; Solids; Substations;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1974.294014
Filename :
4075440
Link To Document :
بازگشت