DocumentCode
1053109
Title
Harmonic measurements from a group connected generator HVDC converter scheme
Author
Macdonald, S.J. ; Enright, W. ; Arillaga, J. ; O´Brien, M.T.
Author_Institution
Canterbury Univ., Christchurch, New Zealand
Volume
10
Issue
4
fYear
1995
fDate
10/1/1995 12:00:00 AM
Firstpage
1937
Lastpage
1943
Abstract
A recent CIGRE document published in ELECTRA has described the potential benefits of a direct connection of generators to HVDC power converters. While many theoretical contributions have been made, no practical test data has become available so far. This paper reports on harmonic tests carried out at the Benmore end of the New Zealand HVDC link operating as a group connected scheme. It was found that the measured harmonic current levels were well below specified generator ratings. Dynamic simulation accurately predicted the harmonic currents whereas the results of a steady state formulation were less-reliable
Keywords
DC transmission networks; HVDC power convertors; HVDC power transmission; electric generators; harmonic distortion; power system harmonics; power system measurement; HVDC power converters; New Zealand; generator ratings; group connected generator; harmonic current levels; harmonic measurements; harmonic tests; Active filters; Costs; HVDC transmission; Power generation; Power harmonic filters; Power system harmonics; Stator windings; Steady-state; Testing; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.473360
Filename
473360
Link To Document