• DocumentCode
    1053109
  • Title

    Harmonic measurements from a group connected generator HVDC converter scheme

  • Author

    Macdonald, S.J. ; Enright, W. ; Arillaga, J. ; O´Brien, M.T.

  • Author_Institution
    Canterbury Univ., Christchurch, New Zealand
  • Volume
    10
  • Issue
    4
  • fYear
    1995
  • fDate
    10/1/1995 12:00:00 AM
  • Firstpage
    1937
  • Lastpage
    1943
  • Abstract
    A recent CIGRE document published in ELECTRA has described the potential benefits of a direct connection of generators to HVDC power converters. While many theoretical contributions have been made, no practical test data has become available so far. This paper reports on harmonic tests carried out at the Benmore end of the New Zealand HVDC link operating as a group connected scheme. It was found that the measured harmonic current levels were well below specified generator ratings. Dynamic simulation accurately predicted the harmonic currents whereas the results of a steady state formulation were less-reliable
  • Keywords
    DC transmission networks; HVDC power convertors; HVDC power transmission; electric generators; harmonic distortion; power system harmonics; power system measurement; HVDC power converters; New Zealand; generator ratings; group connected generator; harmonic current levels; harmonic measurements; harmonic tests; Active filters; Costs; HVDC transmission; Power generation; Power harmonic filters; Power system harmonics; Stator windings; Steady-state; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.473360
  • Filename
    473360