Measurements of dielectric stress in EHV power transformer insulation
Author
Vailles, Christian ; Malewski, Ryszard ; Dai-Do, Xuan ; Aub, Jacques
Author_Institution
ABB-Varennes, Quebec, Que., Canada
Volume
10
Issue
4
fYear
1995
fDate
10/1/1995 12:00:00 AM
Firstpage
1757
Lastpage
1763
Abstract
A relatively high failure rate of the internal insulation of EHV power transformers has been reported by public utilities. This prompted a study of the safety margin of EHV transformers in service and under test. In this project, a number of transient overvoltages were digitally recorded in EHV substations and the transient voltage distribution along the HV winding was measured digitally on many untanked transformers. An evaluation of the safety margin indicates that test impulse waveforms specified in the standards do not always represent system-generated transients, which can jeopardize EHV transformer insulation. The insulation can be designed in such a way to keep a similar safety margin in different parts of the winding, and insulating materials can be used more efficiently
Keywords
computerised instrumentation; dielectric measurement; electric breakdown; insulation testing; overvoltage; power system measurement; power system transients; power transformer insulation; power transformer testing; power transformers; safety; transformer windings; voltage distribution; EHV power transformer insulation; EHV substations; HV winding; dielectric stress measurement; digital measurements; failure rate; internal insulation; public utilities; safety margin; transient overvoltages; transient voltage distribution; Dielectric measurements; Dielectrics and electrical insulation; Power measurement; Power transformer insulation; Power transformers; Safety; Stress measurement; Substations; Surges; Testing;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.473383
Filename
473383
Link To Document