• DocumentCode
    1055436
  • Title

    Phase angle regulating transformer protection

  • Author

    Ibrahim, M.A. ; Stacom, F.P.

  • Author_Institution
    New York Power Authority, White Plains, NY, USA
  • Volume
    9
  • Issue
    1
  • fYear
    1994
  • fDate
    1/1/1994 12:00:00 AM
  • Firstpage
    394
  • Lastpage
    404
  • Abstract
    This paper describes the protection of a 345 kV, 450 MVA three phase, phase angle regulating (PAR) transformer. The transformer includes load tap changers which permit phase angle variations of 25° advance to 25° retard in a total of 32 steps (16 advance, 16 retard). The series unit and the exciting unit of the PAR are mounted in separate tanks, with four throat connections between the tanks (three-single phase primary connections and one-three phase secondary connection). The series unit is rated 86270 V/66122 V with the secondary windings delta connected and the exciting unit rated at 345000 V/67728 V grounded wye-grounded wye. The exciting unit is of three legged core type construction
  • Keywords
    exciters; power transformers; transformer protection; transformer windings; 345 kV; 450 MVA; 66122 V; 67728 V; 86270 V; delta connection; grounded wye; load tap changers; phase angle regulating transformer; phase angle variations; single phase primary connections; three legged core type construction; three phase secondary connection; throat connections; transformer protection; Control systems; Load flow; Power & Energy Society; Power system relaying; Printing; Protection; Silicon compounds; Switches; Virtual colonoscopy; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.277711
  • Filename
    277711