DocumentCode
1055436
Title
Phase angle regulating transformer protection
Author
Ibrahim, M.A. ; Stacom, F.P.
Author_Institution
New York Power Authority, White Plains, NY, USA
Volume
9
Issue
1
fYear
1994
fDate
1/1/1994 12:00:00 AM
Firstpage
394
Lastpage
404
Abstract
This paper describes the protection of a 345 kV, 450 MVA three phase, phase angle regulating (PAR) transformer. The transformer includes load tap changers which permit phase angle variations of 25° advance to 25° retard in a total of 32 steps (16 advance, 16 retard). The series unit and the exciting unit of the PAR are mounted in separate tanks, with four throat connections between the tanks (three-single phase primary connections and one-three phase secondary connection). The series unit is rated 86270 V/66122 V with the secondary windings delta connected and the exciting unit rated at 345000 V/67728 V grounded wye-grounded wye. The exciting unit is of three legged core type construction
Keywords
exciters; power transformers; transformer protection; transformer windings; 345 kV; 450 MVA; 66122 V; 67728 V; 86270 V; delta connection; grounded wye; load tap changers; phase angle regulating transformer; phase angle variations; single phase primary connections; three legged core type construction; three phase secondary connection; throat connections; transformer protection; Control systems; Load flow; Power & Energy Society; Power system relaying; Printing; Protection; Silicon compounds; Switches; Virtual colonoscopy; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.277711
Filename
277711
Link To Document