DocumentCode :
1055436
Title :
Phase angle regulating transformer protection
Author :
Ibrahim, M.A. ; Stacom, F.P.
Author_Institution :
New York Power Authority, White Plains, NY, USA
Volume :
9
Issue :
1
fYear :
1994
fDate :
1/1/1994 12:00:00 AM
Firstpage :
394
Lastpage :
404
Abstract :
This paper describes the protection of a 345 kV, 450 MVA three phase, phase angle regulating (PAR) transformer. The transformer includes load tap changers which permit phase angle variations of 25° advance to 25° retard in a total of 32 steps (16 advance, 16 retard). The series unit and the exciting unit of the PAR are mounted in separate tanks, with four throat connections between the tanks (three-single phase primary connections and one-three phase secondary connection). The series unit is rated 86270 V/66122 V with the secondary windings delta connected and the exciting unit rated at 345000 V/67728 V grounded wye-grounded wye. The exciting unit is of three legged core type construction
Keywords :
exciters; power transformers; transformer protection; transformer windings; 345 kV; 450 MVA; 66122 V; 67728 V; 86270 V; delta connection; grounded wye; load tap changers; phase angle regulating transformer; phase angle variations; single phase primary connections; three legged core type construction; three phase secondary connection; throat connections; transformer protection; Control systems; Load flow; Power & Energy Society; Power system relaying; Printing; Protection; Silicon compounds; Switches; Virtual colonoscopy; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.277711
Filename :
277711