DocumentCode :
1055716
Title :
Voltage Stability Study of the PJM System Following Extreme Disturbances
Author :
Koessler, Rodolfo J. ; Qiu, Wenzheng ; Patel, Mahendra ; Clark, Harrison K.
Author_Institution :
ABB, Inc, Latham, NY
Volume :
22
Issue :
1
fYear :
2007
Firstpage :
285
Lastpage :
293
Abstract :
This paper presents results from an analysis of voltage stability following severe contingencies in the PJM system. The analyses involved the use of steady-state (OPF) and short- and long-term simulation tools. The results highlight the importance of adequate load modeling in assessing the performance of and solutions to voltage instability. Undervoltage load shedding (UVLS) is shown to be beneficial in arresting instability. Optimal power flow (OPF) analyses (supplemented with dynamic simulation results) provide valuable insight into the best locations and required minimum levels of UVLS. However, UVLS may not be able to address the serious scenarios where fast voltage dynamics develop immediately after an outage
Keywords :
load flow; load shedding; power system faults; power system stability; load modeling; optimal power flow analysis; steady-state simulation; undervoltage load shedding; voltage dynamics; voltage stability; Analytical models; Integrated circuit interconnections; Load flow; Load flow analysis; Load modeling; Power system reliability; Power system simulation; Stability analysis; Steady-state; Voltage; Extreme contingencies; fault; short circuit; undervoltage load shedding (UVLS); voltage stability;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2006.887955