    Spacer-Cable Lightning-Induced Overvoltages Computed Using Measured Ground Resistances

  • Author

    Jiang, Grace Ge ; Boggs, Steven ; Tarpey, James W. ; Wamer, Ronald H.

  • Author_Institution
    Electr. Products Div., 3M Austin Center, TX
  • Volume
    43
  • Issue
    1
  • fYear
    2007
  • Firstpage
    202
  • Lastpage
    207
  • Abstract
    Spacer cable provides compact distribution of three-phase power. However, the close proximity of the phases to each other and the neutral carrier wire results in very high fields under lightning conditions. The concept of spacer cable is based on the assumption that the neutral carrier wire is grounded at each pole with an earth resistance no greater than 25 Omega. In many areas, this assumption is far from met. In this paper, we compute lightning-induced overvoltages for long lengths of spacer cable including the effect of every lightning arrester, transformer, etc., on the line and using measured ground resistances, for a range of lightning currents and rise times
  • Keywords
    arresters; earthing; lightning protection; overvoltage protection; power cables; power transformer protection; compact distribution; earth resistance; ground resistance measurement; lightning arrester; neutral carrier wire; spacer-cable lightning-induced overvoltages; three-phase power; transformers; Conductors; Electrical resistance measurement; Lightning; Polyethylene; Power cable insulation; Power cables; Power transformer insulation; Power transformers; Surges; Wire; Grounding; lightning; spacer cable;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2006.887312
  • Filename