Diagnosis of the state of power transformer windings by on-line measurement of stray reactance
Author :
Arri, Ernesto ; Carta, Alessandro ; Mocci, Francesco ; Tosi, Mario
Author_Institution :
Politecnico di Torino, Italy
Volume :
42
Issue :
2
fYear :
1993
fDate :
4/1/1993 12:00:00 AM
Firstpage :
372
Lastpage :
378
Abstract :
A strategy for online diagnosis of the state of the windings in power transformers is discussed. Earlier work showed that it is possible to separately determine core and copper losses of transformers in real operating conditions. A similar measurement is suitable for the online determination, with good precision, of the stray reactance variations in transformers. Since the stray reactance is indicative of windings geometry, this technique enables a diagnostic system to be set up that provides indications of conductor insulation reliability, recommending shutdown when necessary. The method was tested on a 25-MVA-150-kV/16.2-kV three-phase transformer, showing the possibility of performing this online determination with an accuracy at least on the same order as that obtained in the usual methods with a transformer not in service
Keywords :
automatic testing; electric reactance measurement; insulation testing; loss measurement; power transformers; transformer insulation; transformer testing; transformer windings; 150 kV; 16.2 kV; 25 MVA; insulation reliability; losses; online diagnosis; power transformer windings; stray reactance; three-phase transformer; Circuit faults; Conductors; Electrodynamics; IEC standards; Impedance; Power measurement; Power transformers; Stress; Testing; Transformer cores;
fLanguage :
English
Journal_Title :
Instrumentation and Measurement, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9456
Type :
jour
DOI :
10.1109/19.278585
Filename :
278585
Link To Document :
بازگشت