Calculating Mutual Ground Impedances Between Overhead and Buried Cables
Author
Uribe, F.A.
Author_Institution
State Univ. of Guadalajara, Guadalajara
Volume
50
Issue
1
fYear
2008
Firstpage
198
Lastpage
203
Abstract
Aerial and buried electric conductors often share the same right of way. When a phase-to-ground fault occurs, high transient-induced overvoltages appear from short-circuit currents to the ground. The mutual ground-loop impedances between both systems are given by the Pollaczek coupling integral that does not possess an analytic closed-form solution, and its integrand is highly oscillatory to perform a direct numerical integration. An efficient and accurate algorithmic evaluation of the Pollaczek coupling integral is presented in this paper. The obtained result is used in the numerical assessment of approximated formulas previously issued by Lucca, Wedepohl, and Comite Consultatif International Telephonique et Telegraphique.
Keywords
fault diagnosis; integration; overhead line conductors; power transmission faults; power transmission lines; Pollaczek coupling integral; aerial electric conductors; analytic closed-form solution; buried cables; buried electric conductors; direct numerical integration; mutual ground impedances; mutual ground-loop impedances; overhead cables; phase-to-ground fault; short-circuit currents; transient-induced overvoltages; Closed-form solution; Conductors; Frequency; Impedance; Mutual coupling; Performance analysis; Power cables; Skin effect; Surges; Underwater cables; Voltage; Ground return; Pollaczek coupling integral; inductive coupling; numerical integration;
fLanguage
English
Journal_Title
Electromagnetic Compatibility, IEEE Transactions on
Publisher
ieee
ISSN
0018-9375
Type
jour
DOI
10.1109/TEMC.2007.915286
Filename
4446998
Link To Document