• DocumentCode
    1061241
  • Title

    Fault Current Limiter Using YBCO Coated Conductor—The Limiting Factor and Its Recovery Time

  • Author

    Baldan, Carlos A. ; Lamas, Jérika Suely ; Shigue, Carlos Yujiro ; Filho, Ernesto Ruppert

  • Volume
    19
  • Issue
    3
  • fYear
    2009
  • fDate
    6/1/2009 12:00:00 AM
  • Firstpage
    1810
  • Lastpage
    1813
  • Abstract
    A fault current limiter (FCL) based on an arrangement of parallel connected high temperature superconducting tapes constituting a limiter element was designed and tested in 220 V line for a fault current peak between 1 kA to 2 kA. The limiter employed second generation (2G) HTS tapes of YBCO coated conductor reinforced with stainless steel. Four tapes were electrically connected in parallel with 0.4 m effective length per element wherein 16 elements connected in series constitutes a single-phase unit. The FCL performance was evaluated through over-current and current fault tests. Its recovery characteristics were used to design the shunt protection. The designed limiting ratio is 4 for 16 elements and the experimental result for one element showed a 20% limiting ratio. For the fault current test one element can withstand five cycles of fault without degradation. It was observed recovery times below 0.5 s under nominal load using a shunt resistance of 173 mOmega.
  • Keywords
    fault current limiters; high-temperature superconductors; superconducting tapes; 2G HTS tapes; YBa2Cu3O7; conductor; current fault tests; fault current limiter; high temperature superconducting tapes; recovery time; resistance 173 mohm; stainless steel; voltage 220 V; Current limiting ratio; YBCO coated conductor; YBCO recovery characteristics; superconducting fault current limiter;
  • fLanguage
    English
  • Journal_Title
    Applied Superconductivity, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1051-8223
  • Type

    jour

  • DOI
    10.1109/TASC.2009.2019043
  • Filename
    5067233