Title :
Performance of synchronous machines operating with unbalanced armature windings
Author :
Rhudy, R.G. ; Snively, H.D. ; White, J.C.
Author_Institution :
Power Technol. Inc., Schenectady, NY, USA
fDate :
6/1/1988 12:00:00 AM
Abstract :
The performance of synchronous machines operating with armature windings unbalanced by having coils cut out following winding failure is considered. The resulting unbalanced voltages and currents tend to produce overheating and may produce magnetic pull-over or excessive vibration. A method of calculating winding currents and voltages in unbalanced windings is presented. The conditions for winding modification schemes to control magnetic pull-over and severe vibration are discussed. This analysis is also applicable to polyphase induction motors
Keywords :
machine windings; synchronous machines; magnetic pull-over; overheating; polyphase induction motors; synchronous machines; unbalanced armature windings; vibration; winding currents; winding failure; winding voltages; Circuits; Coils; DH-HEMTs; Induction generators; Induction motors; Machine windings; Stator windings; Synchronous machines; Vibrations; Voltage;
Journal_Title :
Energy Conversion, IEEE Transactions on