• DocumentCode
    1064899
  • Title

    Application of a corona onset criterion to calculation of corona onset voltage of stranded conductors

  • Author

    Yamazaki, Kenichi ; Olsen, Robert G.

  • Author_Institution
    Electr. Insulation Dept., Central Res. Inst. of Electr. Power Ind., Iwado-Kita, Japan
  • Volume
    11
  • Issue
    4
  • fYear
    2004
  • Firstpage
    674
  • Lastpage
    680
  • Abstract
    The conditions under which corona first occurs for any set of electrodes are an important design consideration since corona can limit the performance of any given configuration of electrical conductors. Here, the 60 Hz ac corona onset voltage for a stranded wire in air is calculated. The criterion involves the characteristics, i.e. composition and pressure, of the gas in which the conductor is immersed and the electric field in the vicinity of the conductor surface. It is found that the calculated corona onset voltage agrees reasonably well with experimental data and that its behavior as a function of overall conductor radius and number of strands is as expected.
  • Keywords
    corona; electric fields; electrodes; overhead line conductors; surface roughness; 60 Hz; conductor radius; conductor surface; corona onset voltage; electric field; electrical conductors; electrodes; roughness; stranded conductor; stranded wire; surface irregularity; Application software; Conductors; Corona; Electric fields; Electrodes; Power transmission lines; Rough surfaces; Surface roughness; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2004.1324356
  • Filename
    1324356