DocumentCode :
1067736
Title :
Mechanical Fatigue Characteristics of High Voltage Generator Insulation
Author :
Futakawa, Akemi ; Hirabayashi, Shoji ; Tani, Tsutom ; Shibayama, Kyoichi
Author_Institution :
Mitsubishi Electric Corporation 80 Nakano, Minamishimizu, Amagasaki, Hyogo, Japan
Issue :
6
fYear :
1978
Firstpage :
395
Lastpage :
402
Abstract :
This paper presents the deformation and fracture behavior of stator windings subjected to static and cyclic bending loadings, and the reliability of newly developed insulation systems. The flexural deformation characteristics are revealed on the curved end portion of the stator windings for a 1300 MVA water cooled generator. The fatigue characteristics are examined on the test bars with three different kinds of the developed insulation systems. Comparing those results with calculated thermal strain, it has been confirmed that the insulation systems have sufficient mechanical strength to withstand thermal cycling in service.
Keywords :
Bars; Capacitive sensors; Character generation; Epoxy resins; Fatigue; Insulation testing; Lamination; Stator windings; System testing; Voltage;
fLanguage :
English
Journal_Title :
Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9367
Type :
jour
DOI :
10.1109/TEI.1978.298085
Filename :
4080577
Link To Document :
بازگشت