DocumentCode
1067799
Title
Electrical Performance of Oven-Dried XLPE Cable
Author
Chan, J.C.
Author_Institution
Canada Wire and Cable Ltd., Toronto, Ontario, Canada
Issue
6
fYear
1978
Firstpage
444
Lastpage
447
Abstract
Accelerated aging tests conducted on miniature XLPE insulated cable have demonstrated that the oven-drying of steam-cuted XLPE cable insulation at 70°C does not impart any improvement in the initial breakdown voltage or in long-term electrical performance of the insulation over the as-received XLPE samples. Therefore, the oven-drying of steam-cured XLPE cable at 70°C is not considered as an effective method of improving cable quality.
Keywords
Aging; Breakdown voltage; Cable insulation; Dielectrics and electrical insulation; Insulation testing; Moisture; Ovens; Temperature; Trees - insulation; Wire;
fLanguage
English
Journal_Title
Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
0018-9367
Type
jour
DOI
10.1109/TEI.1978.298105
Filename
4080583