DocumentCode :
1067870
Title :
Interarea Model Estimation for Radial Power System Transfer Paths With Intermediate Voltage Control Using Synchronized Phasor Measurements
Author :
Chakrabortty, Aranya ; Chow, Joe H. ; Salazar, Armando
Author_Institution :
Aeronaut. & Astronaut. Dept., Univ. of Washington, Seattle, WA, USA
Volume :
24
Issue :
3
fYear :
2009
Firstpage :
1318
Lastpage :
1326
Abstract :
In this paper we develop measurement-based methods for estimating a two-machine reduced model to represent the interarea dynamics of a radial, two-area power system with intermediate dynamic voltage control. Two types of voltage control equipment are considered, namely, a static VAr compensator (SVC), and a synchronous condenser. The methods use synchronized bus voltage phasor data at several buses including the voltage control bus, and the line currents on the power transfer path.
Keywords :
phase measurement; power system control; power system measurement; static VAr compensators; voltage control; SVC; interarea model estimation; intermediate dynamic voltage control; radial power system transfer paths; static VAr compensator; synchronized bus voltage; synchronized phasor measurement; synchronous condenser; two-machine reduced model; voltage control equipment; Generator voltage support; phasor measurement unit (PMU); power transfer path; static VAr compensator (SVC);
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2009.2022995
Filename :
5071157
Link To Document :
بازگشت