DocumentCode
1068051
Title
In-Service Partial Discharge Testing of Generator Insulation
Author
Kurtz, M. ; Stone, G.C.
Author_Institution
Ontario Hydro, Research Division, Toronto, Canada
Issue
2
fYear
1979
fDate
4/1/1979 12:00:00 AM
Firstpage
94
Lastpage
100
Abstract
Progressive degradation of high-voltage generator insulation, whether due directly to the erosive effects of internal or slot discharge or to other debilitating factors such as heat and vibration, may be detected and monitored as a function of time by in-situ partial-dischargetests. This paper describes new diagnostic test techniques for assessing the condition of generator insulation with a minimum of service interruption. An improved means of coupling or data acquisition is described, as well as a versatile single-channel pulse height analyzer with characteristics a dequate for a field application of this type. Some typical test data are given. These studies were sponsored by the Canadian Electrical Association and are presented with their permission.
Keywords
Aging; Conductors; Filters; Insulation testing; Noise shaping; Partial discharges; Pulse power systems; Pulse shaping methods; Thermal stresses; Vibrations;
fLanguage
English
Journal_Title
Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
0018-9367
Type
jour
DOI
10.1109/TEI.1979.298161
Filename
4080614
Link To Document