DocumentCode
1068377
Title
Designing a New Post Insulator Using 3-D Electric-Field Analysis
Author
Hrastnik, Jo-Çze ; Pihler, Jo-Çze
Author_Institution
Izoelektro d.o.o.
Volume
24
Issue
3
fYear
2009
fDate
7/1/2009 12:00:00 AM
Firstpage
1377
Lastpage
1381
Abstract
Insulators are very important elements of electric power systems. This paper introduces an analysis of electrical conditions in the area between the conductor and the insulator´s upperfitting. The designing of new a composite post insulator is presented with the upperfitting made of insulating material. Previous composite post insulators have had upperfittings made of conducting material metal. 3D analysis of electric-field strength in the insulator and its surroundings are also given. The computation was carried out by using the OPERA Vector Fields program tool. The results of this analysis are presented for both-new and old versions of a composite post insulator. 3D analysis shows that the new version has up to five times lower magnitudes of electric-field strength.
Keywords
composite insulating materials; composite insulators; 3D electric-field analysis; OPERA Vector Fields program tool; composite post insulator; electric power system; insulating material; Electric field; electric-field strength; finite-element method (FEM); medium-voltage post insulator; partial discharge;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2009.2022662
Filename
5071200
Link To Document