• DocumentCode
    1070078
  • Title

    Results of Pollution Tests on Insulators in the ⩾1100 kV Range and Necessity of Testing in the Future

  • Author

    Verma, M.P. ; Petrusch, W.

  • Author_Institution
    F. G. H. EV Mannheim-Rheinau Germany
  • Issue
    3
  • fYear
    1981
  • fDate
    6/1/1981 12:00:00 AM
  • Firstpage
    199
  • Lastpage
    208
  • Abstract
    The necessity of testing at UHV levels depends on the question whether the dielectric strength of polluted insulators is proportional to the insulator length, so that the results at lower voltages can be extrapolated. An analysis of past results of tests on long insulators is presented. The analysis includes evaluation of the corresponding insulation levels in order to show whether the tests have been made in the practical range. The probable voltage drop is computed depending on the available test-circuit ircuit data. The influence of voltage drop on the results is kept in mind while analyzing the results.
  • Keywords
    Dielectric breakdown; Dielectrics and electrical insulation; Flashover; Insulation testing; Insulator testing; Laboratories; Linearity; Pollution; Power transformer insulation; Voltage;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/TEI.1981.298418
  • Filename
    4080834