• DocumentCode
    1070442
  • Title

    Short Time Ac V-t Characteristics of Oil Gaps

  • Author

    Harada, T. ; Aihara, Y. ; Kawamura, T. ; Murano, M. ; Ikeda, M. ; Kumagai, S. ; Inoue, Y. ; Kamata, Y. ; Matsuura, K. ; Watanabe, T. ; Sugimoto, T.

  • Author_Institution
    Central Research Institute of Electric Power Industry
  • Issue
    5
  • fYear
    1981
  • Firstpage
    423
  • Lastpage
    430
  • Abstract
    The High Voltage Test Committee of the Institute of Electrical Engineers of Japan has investigated the ac V-t characteristics of insulating oil with the participation of seven Japanese transformer manufacturers. The breakdown time ranges from a few seconds to 20 minutes after the voltage application when Rogowsky type electrodes of 7.5 mm gap length were used. If the breakdown voltage V of the above results is represented by V ¿ t-1/n, then n takes an average value of 15.5, and it scatters between 11.6 and 23.7 at the 95% confidence limits. From the results of these data, the time conversion factor of the 10-minute withstand voltage was investigated to obtain a more reasonable value for on-site testing of 500 kV transmission equipment ent in Japan.
  • Keywords
    Breakdown voltage; Dielectrics and electrical insulation; Electrodes; Insulation testing; Manufacturing industries; Oil insulation; Petroleum; Power system reliability; Power transformer insulation; Scattering;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/TEI.1981.298438
  • Filename
    4080872