DocumentCode
1070602
Title
Apparatus for Continuously Monitoring Hydrogen Gas Dissolved in Transformer Oil
Author
Tsukioka, H. ; Sugawara, K. ; Mori, E.
Author_Institution
Hitachi Research Laboratory Hitachi Ltd, Hitachi-city, Japan
Issue
6
fYear
1981
Firstpage
502
Lastpage
509
Abstract
This report presents an apparatus for continuously monitoring of hydrogen gas dissolved in transformer oil, in which a polyimide membrane is used to separate the hydrogen from the oil. The hydrogen is allowed to permeate through the membrane and contact a gas sensor every 72 hours. The characteristics of the permeation of the hydrogen gas through the polyimide membrane and of the detection of the hydrogen gas by the gas sensor are described under various conditions. Problems encountered when the apparatus is installed on a tran are also studied and solved. As a result, this new apparatus was found useful in determining whether a transformer is operating normally or not.
Keywords
Biomembranes; Gas detectors; Gas insulation; Gases; Hydrogen; Monitoring; Oil insulation; Petroleum; Polymers; Power transformer insulation;
fLanguage
English
Journal_Title
Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
0018-9367
Type
jour
DOI
10.1109/TEI.1981.298381