• DocumentCode
    1070602
  • Title

    Apparatus for Continuously Monitoring Hydrogen Gas Dissolved in Transformer Oil

  • Author

    Tsukioka, H. ; Sugawara, K. ; Mori, E.

  • Author_Institution
    Hitachi Research Laboratory Hitachi Ltd, Hitachi-city, Japan
  • Issue
    6
  • fYear
    1981
  • Firstpage
    502
  • Lastpage
    509
  • Abstract
    This report presents an apparatus for continuously monitoring of hydrogen gas dissolved in transformer oil, in which a polyimide membrane is used to separate the hydrogen from the oil. The hydrogen is allowed to permeate through the membrane and contact a gas sensor every 72 hours. The characteristics of the permeation of the hydrogen gas through the polyimide membrane and of the detection of the hydrogen gas by the gas sensor are described under various conditions. Problems encountered when the apparatus is installed on a tran are also studied and solved. As a result, this new apparatus was found useful in determining whether a transformer is operating normally or not.
  • Keywords
    Biomembranes; Gas detectors; Gas insulation; Gases; Hydrogen; Monitoring; Oil insulation; Petroleum; Polymers; Power transformer insulation;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/TEI.1981.298381
  • Filename
    4080889