DocumentCode :
1070617
Title :
Environmental Effects on the Rate of Aging of EP-Insulated Power Cable
Author :
Wilkens, W.D.
Author_Institution :
Anaconda-Ericsson Inc. Wire and Cable Division Insulated Products Engineering Center Marion, Indiana
Issue :
6
fYear :
1981
Firstpage :
521
Lastpage :
527
Abstract :
The accurate prediction of service life of extruded dielectric power cables from relatively short-term laboratory tests has been, and continues to be, a challenge for power cable engineers. Incomplete understanding of failure mechanisms and the effect of the many different in-service environmental factors, possible interactions between these factors, and the widely scattered nature of dielectric phenomena contribute to the uncertainties. In this laboratory investigation of the effects of water, water temperature, air temperature, voltage impulses, current loading and their interactions on a shielded 5 kV ethylene propylene rubber (EP) insulated power cable, water and water temperature were found to have the largest effect on dielectric strength. When aged in air for 3 years at 4.5 times rated voltage (the least harmful condition found in the experiment) the average dielectric strength declined to 92% of the original value; however this decline is not statistically significant. When aged in 35°C water for 3 years at 4.5 times rated voltage (the most harmful condition found in the experiment) the dielectric strength declined to 21% of the orginal value.
Keywords :
Aging; Dielectric breakdown; Environmental factors; Failure analysis; Laboratories; Life testing; Power cables; Power engineering and energy; Temperature; Voltage;
fLanguage :
English
Journal_Title :
Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9367
Type :
jour
DOI :
10.1109/TEI.1981.298383