DocumentCode
1070958
Title
Testing and Demonstration Results of the 350 m Long HTS Cable System Installed in Albany, NY
Author
Weber, C.S. ; Lee, Ron ; Ringo, Steven ; Masuda, Takato ; Yumura, Hiroyasu ; Moscovic, Jon
Author_Institution
SuperPower Inc., Schenectady
Volume
17
Issue
2
fYear
2007
fDate
6/1/2007 12:00:00 AM
Firstpage
2038
Lastpage
2042
Abstract
The Albany Cable Project team (BOC, National Grid, Sumitomo Electric, SuperPower) have built and tested a 350-m long HTS cable and cryogenic system rated at 48 MVA (800 Arms, 34.5-kV). The cable system included the world´s first demonstration of an HTS cable-to-cable joint (or splice) as well as some novel design aspects in both the cryogenic refrigeration system and the terminations. The cable was installed and began operation in July 2006. This paper will summarize the testing and operational aspects of the HTS cable system and its integration into the existing national grid 34.5-kV network.
Keywords
high-temperature superconductors; refrigeration; superconducting cables; Albany Cable Project team; HTS cable system; cryogenic refrigeration system; current 800 A; voltage 34.5 kV; Bismuth compounds; Cryogenics; High temperature superconductors; Personnel; Power industry; Refrigeration; Research and development; Superconducting cables; System testing; Wire; Cryogenic refrigeration systems; HTS cables; high-temperature superconductors; superconducting cables;
fLanguage
English
Journal_Title
Applied Superconductivity, IEEE Transactions on
Publisher
ieee
ISSN
1051-8223
Type
jour
DOI
10.1109/TASC.2007.899828
Filename
4277805