• DocumentCode
    1072853
  • Title

    New Apparatus for Detecting H2, CO, and CH4 Dissolved in Transformer Oil

  • Author

    Tsukioka, H. ; Sugawara, K. ; Mori, E. ; Hukumori, S. ; Sakai, S.

  • Author_Institution
    Hitachi Research Laboratory Hitachi Ltd., Hitachi City, Japan
  • Issue
    4
  • fYear
    1983
  • Firstpage
    409
  • Lastpage
    419
  • Abstract
    This report presents a new method of separating H2, CO, CH4, C2H2, C2H4, and C2H6 dissolved in transformer oil and detecting H2, CO, and CH4, in which a tetrafluoroethylene-perfluoroalkylvinylether copolymer membrane is used to separate gases from the oil. The quantities of H2, CO, and CH4 that permeated through the membrane were relatively large. These gases were detected with a new gas detector, which consists of a catalytic gas sensor and a gas chromatograph, and which uses air as the carrier gas. Compared with conventional methods of gas analysis, H2, CO, and CH4 dissolved in transformer oil can be analyzed simply and inexpensively with this method. As a result, this new method should prove useful in determining whether a transformer is operating normally or not.
  • Keywords
    Biomembranes; Cities and towns; Dissolved gas analysis; Gas detectors; Gases; Hydrogen; Oil insulation; Petroleum; Polymers; Power transformer insulation;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/TEI.1983.298680
  • Filename
    4081125