DocumentCode
1073480
Title
Experience with return voltage measurements for assessing insulation conditions in service-aged transformers
Author
Saha, Tapan Kumar ; Yao, Zheng Tong
Author_Institution
Sch. of Inf. Technol. & Electr. Eng., Univ. of Queensland, Brisbane, Australia
Volume
18
Issue
1
fYear
2003
fDate
1/1/2003 12:00:00 AM
Firstpage
128
Lastpage
135
Abstract
This paper describes the investigation of the insulation condition of a number of power and distribution type transformers of different manufacturing dates and with different operating histories. Return voltage measurements were conducted for these transformers. Effects of moisture and aging on the oil-paper insulation of these transformers were investigated and results are presented in this paper. Moisture in oil samples at known temperature was measured for these transformers. Previously accelerated aging experiments were performed on paper wrapped insulated conductors in different environments over a temperature range of 115 to 145°C. Results from the measurements on transformers are compared with those of the accelerated aged samples and are described in this paper.
Keywords
ageing; condition monitoring; electric breakdown; insulation testing; life testing; power transformer insulation; power transformer testing; voltage measurement; 115 to 145 C; aging; condition monitoring; dielectric measurement; insulation life; moisture; oil-paper insulation; paper wrapped insulated conductors; return voltage measurements; service-aged transformer insulation condition assessment; Accelerated aging; Conductors; History; Moisture measurement; Oil insulation; Petroleum; Power transformer insulation; Pulp manufacturing; Temperature measurement; Voltage measurement;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2002.803722
Filename
1159908
Link To Document