• DocumentCode
    1073594
  • Title

    Analysis of Weibull Distribution for Electrical Breakdown Voltage o Stator Windings

  • Author

    Hakamada, Takeshi

  • Author_Institution
    Hitachi Works, Hitachi, Ltd. Hitachi-city, Japan
  • Issue
    2
  • fYear
    1984
  • fDate
    4/1/1984 12:00:00 AM
  • Firstpage
    114
  • Lastpage
    118
  • Abstract
    Because plant systems are growing, motors need to be more reliable. Preventaive maintenance has therefore become more important. The authors reported nondestructive measurements for insulation diagnosis and recommended the optimum time of rewinding in earlier papers [1-2]. As part of this research series, this paper analyses how the Weibull distribution of the breakdown voltage changes in relation to operating years. This analysis was performed on 75 motors which had been used for 15 to 23 years in many thermal power plants. Results show that the deterioration of windings begins mainly wit thermal stress; then vibration, a form of mechanical stress, makes some delaminations and/or hair cracks in the insulation. Finally, moisture absorption, an environmental stress factor, affects the system and results in electrical breakdown paths. Through these steps, the Weibull shape parameter changes drastically from an initial high value to a final low value. The details are described below.
  • Keywords
    Delamination; Insulation; Maintenance; Performance analysis; Power generation; Stator windings; Thermal stresses; Time measurement; Vibrations; Weibull distribution;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/TEI.1984.298782
  • Filename
    4081206