    Experimental facility for investigation of lightning performance of distribution lines

  • Author

    Nakada, Kazuo ; Sugimoto, Hitoshi ; Yokoyama, Shigeru

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Hokuriku Electr. Power Co., Tokyo, Japan
  • Volume
    18
  • Issue
    1
  • fYear
    2003
  • fDate
    1/1/2003 12:00:00 AM
  • Firstpage
    253
  • Lastpage
    257
  • Abstract
    In order to clarify the lightning performance of a distribution line, test distribution lines and a test tower were constructed at the Mikuni Testing Center of Hokuriku Electric Power Company in 1999. Using these facilities, the authors observed transient voltages and current distributions due to direct strokes of natural lightning. Based on this data, we have clarified the following points: (1) calculated voltages and currents using the EMTP agree with the experimental results fairly well; and (2) for lightning currents of long durations, however, the reduction of voltages across arresters by energy absorption should be taken into consideration.
  • Keywords
    EMTP; current distribution; power distribution faults; power distribution lines; power distribution protection; power system analysis computing; power system measurement; power system transients; test facilities; ENITP; Japan; current distributions; distribution lines lightning performance; test distribution lines; test tower; transient voltages; Arresters; Current distribution; EMTP; Grounding; Lightning; Poles and towers; Power system transients; Surges; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2002.803844
  • Filename
    1159927