DocumentCode :
1074547
Title :
Universal Adaptive Differential Protection for Regulating Transformers
Author :
Hayder, Tammam ; Schaerli, Ulrich ; Feser, Kurt ; Schiel, Ludwig
Author_Institution :
Univ. of Stuttgart, Stuttgart
Volume :
23
Issue :
2
fYear :
2008
fDate :
4/1/2008 12:00:00 AM
Firstpage :
568
Lastpage :
575
Abstract :
Since regulating transformers have proved to be efficient in controlling the power flow and regulating the voltage, they are more and more widely used in today´s environment of energy production, transmission and distribution. This changing environment challenges protection engineers as well to improve the sensitivity of protection, so that low-current faults could be detected (like turn-to-turn short circuits in transformer windings) and a warning message could be given. Moreover, the idea of an adaptive protection that adjusts the operating characteristics of the relay system in response to changing system conditions has became much more promising. It improves the protection sensitivity and simplifies its conception. This paper presents an adaptive adjustment concept in relation to the position change of the on load tap changer for universal differential protection of regulating transformers; such a concept provides a sensitive and cost-efficient protection for regulating transformers. Various simulations are carried out with the Electro-Magnetic Transients Program/Alternative Transients Program. The simulation results indicate the functional efficiency of the proposed concept under different fault conditions; the protection is sensitive to low level intern faults. The paper concludes by describing the software implementation of the algorithm on a test system based on a digital signal processor.
Keywords :
EMTP; fault currents; on load tap changers; power transformer protection; regulation; EMTP; Electromagnetic Transients Program; adaptive differential protection; alternative transients program; cost-efficient protection; digital signal processor; fault detection; low-current faults; on load tap changer; regulating transformers; relay system; Differential protection; Electromagnetic Transients Program (EMTP); phase shifters; regulating transformer; tap changer;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2008.916758