• DocumentCode
    1077319
  • Title

    Partial Discharges in Electrical Insulation under Combined Alternating and Impulse Stresses

  • Author

    Densley, R.J.

  • Author_Institution
    Radio and Electrical Engineering Division, National Research Council of Canada, Ottawa, Canada
  • Issue
    4
  • fYear
    1970
  • Firstpage
    96
  • Lastpage
    103
  • Abstract
    A study has been made of the partial discharge characteristics of artificial cavities in polyethylene under combined 60-Hz and negative 1.2/50-¿s impulse stresses, the amplitude of the altemating stress being below discharge inception value. Samples of cross-linked and low-density polyethylenes were tested. The discharge sequence was derived from the results of previous tests, which used only impulse stresses. It showed that the ac discharges, initiated by an impulse, could continue indefinitely under certain conditions. The experimental results do not confirm this but show that the ac discharges always extinguish within 10 seconds after the application of the impulse. The number of ac discharges, although independent of the amplitude of the impulse, increases with increasing altemating stress but decreases as the sample ages. The effect of the angle of the cycle at which the impulse was applied on the combined discharge inception stress is also described.
  • Keywords
    Breakdown voltage; Dielectrics and electrical insulation; Gas insulation; Impulse testing; Partial discharges; Performance evaluation; Polyethylene; Production facilities; Solids; Stress;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/TEI.1970.299117
  • Filename
    4081613