DocumentCode
1077469
Title
Voltage Surge Performance of Vacuum-Insulated Cryo-Cable
Author
Graneau, Peter ; Jeanmonod, John
Author_Institution
Underground Power Corporation, Weston, Mass. 02193
Issue
1
fYear
1971
fDate
3/1/1971 12:00:00 AM
Firstpage
39
Lastpage
47
Abstract
This paper describes the results obtained from two short experimental lengths of single-phase vacuum-insulated cables, one of which can be cooled by liquid nitrogen. Using a variety of high-voltage sources, it has been shown that there is little correlation between the energy of the source and the damage produced by sparks. Hence, the chances seem good that a cryo-cable connected to a bulk power transmission system will not suffer catastrophically with each internal spark.
Keywords
Cable insulation; Conductors; Dielectrics and electrical insulation; Power transmission; Sparks; Surges; Testing; Underground power cables; Voltage; Wire;