DocumentCode :
1078485
Title :
AC breakdown characteristics of in-service aged XLPE distribution cables
Author :
Bartnikas, R. ; Pélissou, S. ; St.-Onge, H.
Author_Institution :
Inst. de Recherche d´´Hydro-Quebec, Varennes, Que., Canada
Volume :
3
Issue :
2
fYear :
1988
fDate :
4/1/1988 12:00:00 AM
Firstpage :
454
Lastpage :
462
Abstract :
AC breakdown tests were performed on field-aged XLPE distribution cables. For these measurements, a special test assembly consisting of air/distilled water terminations was developed. The tested cable specimens were examined for the occurrence of halos and water trees. The results suggest a correlation between the AC breakdown strength and operating stress. The incidence of halos is also found to be related to the AC breakdown strength, but no such relation appears to exist for the water tree length or density
Keywords :
cable insulation; distribution networks; electric breakdown; insulation testing; polymers; power cables; AC breakdown tests; XLPE distribution cables; breakdown strength; cable insulation; halos; insulation testing; operating stress; test assembly; water trees; Aging; Assembly; Cable insulation; Corona; Degradation; Dielectrics and electrical insulation; Electric breakdown; Performance evaluation; Testing; Trees - insulation;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.4280
Filename :
4280
Link To Document :
بازگشت