DocumentCode
1081680
Title
Design and dynamic response characteristics of 400 MW adjustable speed pumped storage unit for Ohkawachi Power Station
Author
Kuwabara, Takao ; Shibuya, Akira ; Furuta, Hideo ; Kita, Eizou ; Mitsuhashi, Keiichi
Author_Institution
Hitachi Ltd., Tokyo, Japan
Volume
11
Issue
2
fYear
1996
fDate
6/1/1996 12:00:00 AM
Firstpage
376
Lastpage
384
Abstract
At 400 MW, the world´s largest adjustable speed pumped storage unit for Ohkawachi Power Station, the Kansai Electric Power Co., Inc., Japan, was commissioned on Dec. 3, 1993. It can change power in steps of at least 32 MW in the generate mode and at least 80 MW in the pump mode, within 0.2 s. This paper describes principal design considerations for the control systems of the machine and presents actual performance of the machine with reference to some typical oscillograph charts
Keywords
dynamic response; machine control; oscillographs; power station control; pumped-storage power stations; variable speed gear; 400 MW; Japan; Kansai Electric Power Company; Ohkawachi Power Station; adjustable speed pumped storage unit; design considerations; dynamic response characteristics; generate mode; oscillograph charts; pump mode; AC generators; Automatic control; Control systems; Power generation; Power generation economics; Power systems; Pumps; Reactive power control; Regulators; Rotors;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/60.507649
Filename
507649
Link To Document