• DocumentCode
    1083587
  • Title

    Test and simulation of network dynamic response using SSFR and RTDR derived synchronous machine models

  • Author

    Rusche, P.A.E. ; Brock, G.J. ; Hannett, L.N. ; Willis, J.R.

  • Author_Institution
    Consumers Power Co., Jackson, MI, USA
  • Volume
    5
  • Issue
    1
  • fYear
    1990
  • fDate
    3/1/1990 12:00:00 AM
  • Firstpage
    145
  • Lastpage
    155
  • Abstract
    The comparative testing of four 60 Hz two-pole generators indicates practical advantages for the SSFR (standstill frequency response) method over the RTDR (rotating time-domain response) method when synchronous machine models are to be synthesized from test data for network dynamic performance analysis. Manufacturer-provided data are compared to SSFR and RTDR derived parameters. All adequately duplicate synchronization, load rejection, and line switching tests. Deterministic sensitivity of CFCT (critical fault clearing time) to selected machine parameters is reported
  • Keywords
    power systems; synchronous machines; 60 Hz; critical fault clearing time; line switching tests; load rejection; network dynamic response; rotating time-domain response; simulation; standstill frequency response; synchronous machine models; two-pole generators; Circuit testing; Couplings; Data acquisition; Equivalent circuits; Manufacturing; Network synthesis; Notice of Violation; Performance analysis; Power & Energy Society; Power generation; Power measurement; Printing; Strontium; Synchronous machines; Virtual manufacturing;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.50826
  • Filename
    50826