Title :
New differential protection scheme for tapped transmission line
Author :
Bhalja, B. ; Maheshwari, R.P.
Author_Institution :
Dept. of Electr. Eng., Indian Inst. of Technol. Roorkee, Roorkee
fDate :
3/1/2008 12:00:00 AM
Abstract :
The development of a new differential protection scheme for tapped transmission lines using wavelet transform is presented. At each relay locations, using the most suitable mother wavelet, the measured three line currents are decomposed up to third level. Thereafter, third-level approximation coefficients are reconstructed and used to derive the operating and restraining quantities. The proposed scheme has been tested extensively using the PSCAD/EMTDC software package with fault data, generated by modelling UKAI-KAKRAPAR 400 kV line of the Indian power system. The proposed scheme eliminates many of the problems encountered with tapped transmission lines such as high resistance faults, out feed current in case of internal and external faults, insufficient current for tripping and provides better discrimination between external and internal faults in case of loss of generation at one end. At the end, a comparative evaluation of the conventional current differential protection scheme with the proposed scheme is also presented. Dependability and security have been studied separately.
Keywords :
power system CAD; power system relaying; power system security; power transmission lines; power transmission protection; wavelet transforms; Indian power system; PSCAD/EMTDC software package; UKAI-KAKRAPAR line; approximation coefficients; differential protection scheme; external faults; fault data; internal faults; relay locations; tapped transmission line; three line currents; voltage 400 kV; wavelet transform;
Journal_Title :
Generation, Transmission & Distribution, IET
DOI :
10.1049/iet-gtd:20070152