Abstract
A hybrid circuit breaker consists of a series-connected vacuum- and SF6 interrupter. The vacuum interrupter has the function to withstand very steep-rising transient recovery voltages, whereas the SF6 interrupter is stressed with the peak of it. Full scale tests are described of a 145-kV prototype, which is subjected to short-line faults based on 63 kA. During these tests, current through the breaker and voltages across both interrupters were monitored with a high-resolution measurement system. It is shown that the principal idea works correctly. From measured results, it is demonstrated that the interaction between the two arcs of completely different physical nature has a positive effect on the interruption: Immediately before current zero, the SF6 arc assists the vacuum arc to interrupt, whereas after current zero, the vacuum arc assists the SF6 arc in the recovery against the recovery voltage. From the analysis of the measurements, it becomes clear that high values of post arc current (up to 30 A) have (at least initially) a positive effect on the breaker performance. Detailed modeling of the interaction of arc-arc and arc-circuit is described, showing a good agreement with the measured results. The model is used to predict the voltage distribution across both interrupters when other (capacitive) voltage grading is applied in the design than present during the tests.
Keywords
SF6 insulation; vacuum arcs; vacuum circuit breakers; vacuum interrupters; SF6 arcs; SF6 interrupter; arc-arc interaction; high-current interruption; hybrid circuit breaker; series-connected vacuum-interrupter; steep-rising transient recovery voltages; vacuum arcs; vacuum interrupter; voltage distribution; Circuit breakers; Circuit faults; Circuit testing; Current measurement; Interrupters; Prototypes; Sulfur hexafluoride; System testing; Vacuum arcs; Voltage; Arc modeling; SF6 interrupter; circuit analysis; high-frequency measurement; high-voltage techniques; hybrid circuit breaker; short-circuit current; testing; vacuum interrupter;
fLanguage
English
Journal_Title
Plasma Science, IEEE Transactions on
Publisher
ieee
ISSN
0093-3813
Type
jour
DOI
10.1109/TPS.2007.896919
Filename
4287085
Link To Document