DocumentCode :
1090715
Title :
Accelerated protection of distribution systems with tapped off loads
Author :
Bo, Z.Q. ; Dong, X.Z. ; Caunce, B.R.J.
Author_Institution :
Energy Autom. & Inf., AREVA T&D Ltd., Stafford, UK
Volume :
151
Issue :
4
fYear :
2004
fDate :
7/11/2004 12:00:00 AM
Firstpage :
461
Lastpage :
468
Abstract :
The paper presents a technique for accelerated protection of distribution systems with tapped off loads. In the technique, the sequence and superimposed signals are used to determine the remote circuit breaker operation, from which a decision on whether a fault is inside the protected section can be made. Extensive simulation studies with respect to a typical ring main system with tapped off loads show that the proposed technique is able to significantly increase the speed of response of the conventional time-grading-based protection scheme.
Keywords :
circuit breakers; power distribution faults; power distribution protection; power system simulation; accelerated protection; circuit breaker operation; distribution systems; faults; ring main distribution system; sequence signals; superimposed signals; tapped off loads;