• DocumentCode
    1094767
  • Title

    The effects of fixture type and HVAC integration on fluorescent lamp/ballast performance

  • Author

    Siminovitch, Michael J. ; Rubinstein, Francis M. ; Verderber, Rudolph R.

  • Author_Institution
    Lawrence Berkeley Lab., Berkeley, CA, USA
  • Volume
    24
  • Issue
    3
  • fYear
    1988
  • Firstpage
    365
  • Lastpage
    369
  • Abstract
    The effects of fixture type and lamp compartment air extract on lamp/ballast performance are described. A luminate/plenum/HVAC simulator was used to measure minimum lamp-wall temperature inside four fixture types while varying lamp-compartment extract conditions. Experimental data show that the lumen output of the lamp/ballast system varies by 20% and system efficacy by 10% depending on the type of fixture and lamp-compartment extract technique used
  • Keywords
    fluorescent lamps; HVAC integration; fixture type; fluorescent lamp/ballast performance; lamp compartment air extract; lumen output; system efficacy; Data mining; Electronic ballasts; Fixtures; Fluorescent lamps; Instruments; Laboratories; Temperature measurement; Testing; Thermal factors; Thermistors;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/28.2883
  • Filename
    2883