  • Abstract
    This paper provides information on laboratory performance of 15 and 35 kV premolded joints from three manufacturers. Data on partial discharge, ac and hot impulse voltage breakdown tests, and dissection of breakdowns are presented for joints that were tested immediately after their assembly and after one year aging immersed in room temperature water (15-30degC), under operating voltage. The test program was repeated twice using joints acquired with a two-year interval. The two batches showed similar performance indicating that all three manufacturers provide consistent quality joints. AC breakdown strength of the joints practically did not change with aging. In contrast, their impulse breakdown strength decreased noticeably. Joints having partial discharge levels up to 5000 pC were included in the study. No obvious correlation was found between the presence of partial discharge and the joints ultimate dielectric strength.
  • Keywords
    electric breakdown; partial discharges; power cables; AC breakdown strength; impulse breakdown strength; laboratory evaluation; medium voltage cables; partial discharge; premolded joints; 15 and 35 kV class; AC; dielectric breakdown; impulse; medium voltage (MV); partial discharge (PD); power cable joints; premolded;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2007.915909
  • Filename
    4469967