DocumentCode
1097131
Title
Comparative Laboratory Evaluation of Premolded Joints for Medium Voltage Cables
Author
Yaroslavskiy, Vitaliy ; Walker, Michael L. ; Katz, Carlos ; Keefe, Robert J.
Author_Institution
Cable Technol. Labs., Brunswick
Volume
23
Issue
2
fYear
2008
fDate
4/1/2008 12:00:00 AM
Firstpage
516
Lastpage
522
Abstract
This paper provides information on laboratory performance of 15 and 35 kV premolded joints from three manufacturers. Data on partial discharge, ac and hot impulse voltage breakdown tests, and dissection of breakdowns are presented for joints that were tested immediately after their assembly and after one year aging immersed in room temperature water (15-30degC), under operating voltage. The test program was repeated twice using joints acquired with a two-year interval. The two batches showed similar performance indicating that all three manufacturers provide consistent quality joints. AC breakdown strength of the joints practically did not change with aging. In contrast, their impulse breakdown strength decreased noticeably. Joints having partial discharge levels up to 5000 pC were included in the study. No obvious correlation was found between the presence of partial discharge and the joints ultimate dielectric strength.
Keywords
electric breakdown; partial discharges; power cables; AC breakdown strength; impulse breakdown strength; laboratory evaluation; medium voltage cables; partial discharge; premolded joints; 15 and 35 kV class; AC; dielectric breakdown; impulse; medium voltage (MV); partial discharge (PD); power cable joints; premolded;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2007.915909
Filename
4469967